Application · access control

Bollard & Access Control Power

Rising bollards, intercoms, card readers and gate barriers sit at the edge of a site where mains is absent or expensive to bring. PoF delivers data and up to 12 W over one hybrid cable to 200 m, with the control cabinet indoors.

Updated October 24, 2026

Copper limit
100 m
PoF limit
200 m
PoF power
12 W / port
PON reach
20 km

The engineering problem

Why the obvious answer fails.

The endpoint is small; the distance, the power and the environment are not. Three paragraphs explain where the design usually breaks.

Access control devices live at the boundary: a bollard at the driveway, an intercom at the gate, a card reader at the pedestrian entrance, a barrier at the exit. The mains distribution board is inside the building, often 50–200 m away. Trenching a mains duct to each column is expensive and may be impossible on a leased site or a heritage facade.

The loads are modest but safety-related. A card reader is 5–12 W; an intercom with a screen and camera is 10–20 W; a rising bollard’s hydraulic pump is a different class (often 1–3 kW and not a PoF load). PoF is suitable for the reader, intercom, camera and control electronics, not for the bollard motor.

Reliability matters more than cost. If the reader loses power, the gate stops. A PoF splitter in the building with a UPS-backed 48 V supply keeps the readers and intercom alive during a mains outage, while the bollard motor remains on its own circuit.

Path comparison

Four paths, one decision.

The correct path is the one that matches the endpoint power, the distance and the presence of mains. Do not compare only on cable price.

PathReachPower at the endpointMains at endpointBest forLimits
Copper PoE100 m channel15.4 / 30 W at the source (af / at)Required for the switchDevices within 100 m of a powered cabinetCable loss, surge path, no reach beyond 100 m
PoE extender200 – 500 m with hopsReduced at each hopRequired at every extenderRetrofit where a mid-point has powerAnother powered box outdoors; still copper
Power over FiberUp to 200 m per portUp to 12 W per portNot requiredCeiling APs, pole cameras, readers, sensors12 W per port, hybrid cable, 200 m limit
Fibre + local PoE switch20 km PON backhaulLocal switch budgetRequired at the local cabinetCabinets, buildings, dense clustersNeeds a powered cabinet and a switch

The correct path is the one that matches the endpoint power, the distance and the presence of mains. Do not compare only on cable price.

Design approach

How we lay it out.

01

Separate the motor from the electronics

Do not try to power a bollard pump over PoF. Put the motor on its own mains circuit and use PoF for the reader, intercom, camera and controller at the column.

02

Put the splitter indoors

Mount the PoF splitter and its 48 V supply in the building, on a UPS if the gate must work during an outage. The hybrid cable runs to the column; the electronics are protected indoors.

03

Keep one cable per column

One hybrid cable carries data and power to each column. That removes the separate signal and mains conduits and limits the copper path to the last 200 m.

Bill of materials

A starting BOM.

Quantities follow the endpoint count and the number of cabinets. Adjust after the site survey.

ItemSpecificationQuantity basis
PoF splitter8 outputs, 12 W per port, 48 V DC1 per 8 columns/devices
Hybrid PoF cableG.657A2 + copper, 20/50 m1 per column + spare
PoF ONU / media converter1× XPON + 1× GE1 per column or group
Access controllerReader / intercom interfacePer design
UPS-backed 48 V supplySized to the splitter load1 per cabinet
SPDAt the building entry and columnPer local code

The bollard motor is not a PoF load. Keep it on a separate mains circuit with its own protection.

Numbers to check

The design rules.

Design ruleValue to confirm
PoF reach200 m
PoF power12 W per port
Reader load5 – 12 W
Intercom load10 – 20 W; check peak
Bollard motorSeparate mains circuit, not PoF
BackupUPS the 48 V supply for gate electronics
Send the site data

Application FAQ

Bollard & Access Control Power: site questions.

If your question is not here, send the site details and we will answer with the calculation, not a brochure.

Ask an engineer

Can PoF power a rising bollard?

No. The hydraulic pump draws far more than 12 W and is a motor load. Use PoF for the reader, intercom and camera at the column; keep the motor on a dedicated mains circuit.

What happens during a power cut?

If the 48 V supply is on a UPS, the readers and intercom stay alive and the gate can be operated manually or by the controller. The bollard motor still needs mains or its own backup.

How far can the column be from the building?

Up to 200 m on PoF. Beyond that, use a local cabinet with a PoE switch and a mains feed, or a fibre link with a local power source.

Is one hybrid cable enough for a reader and a camera?

One cable carries one optical path and one power pair. If the reader and camera are separate devices, use a small PoE switch or a PoF ONU with multiple ports at the column.

Can I use PoF outdoors?

Yes with UV-rated conduit, a drip loop and an IP-rated enclosure for the connectors. The cable is rated −20 to +80 °C, but the jacket is not a substitute for mechanical protection.

Does PoF work with third-party access controllers?

The PoF link is transparent to Ethernet; the controller sees a standard network link. Confirm the connector type and the PoE class of the device at the column.

Next step

Planning Bollard & Access Control Power?

Send the device list, the longest run, the mains condition and the country. We return the path, the BOM and the budget assumptions.

No obligation. The plan states its assumptions so your engineer can check it.